Sign In | Join Free | My himfr.com |
|
Ask Lasest Price | |
Brand Name : | Pepperl+Fuchs |
Model Number : | HiC2025 |
Certification : | COO & COC |
Price : | $100 |
Payment Terms : | T/T,Alipay,Paypal |
Supply Ability : | 99+ |
Delivery Time : | 3-5 days |
Pepperl+Fuchs HiC2025 SMART Transmitter Power Supply 1ch isolated barrier 24VDC
Product Positioning
The HiC2025 is a classic model in the Hi series isolation barrier
from Pepperl+Fuchs, Germany. It is designed to provide
intrinsically safe power and signal isolation for two-wire smart
transmitters (supporting HART/BRAIN protocols) in hazardous
locations such as Zone 0, Zone 1, and Zone 2. It converts 24 V DC
loop power into a safe 4-20 mA signal and provides 2.5 kV three-way
isolation (input, output, and power) between the hazardous and safe
areas of the field, ensuring reliable system operation and the
safety of personnel and equipment.
Core Features
• Intelligent Communication: Bidirectional digital signals are
transmitted without loss. HART, BRAIN handheld communicators, or
AMS device management systems can communicate directly with field
transmitters from the control room, enabling remote configuration,
diagnostics, and asset optimization.
• High-Precision Conversion: Typical transmission error ≤ 0.1% and
temperature drift ≤ 50 ppm/K meet the needs of high-precision
process control. • Fail-Safe: Built-in short-circuit, reverse
polarity, overload, and line-break protection; SIL 2/SC 3
functional safety certification, compliant with IEC 61508/IEC 61511
safety instrumented systems.
• Flexible Output: Supports both source and sink wiring modes,
compatible with various DCS/PLC card requirements.
• Field-Friendly: Ultra-thin 12.5 mm housing, DIN rail mounting,
pluggable terminals, maintenance without powering off; front panel
labeling for easy circuit identification.
Technical Specifications
Power Side (Safe Area)
• Supply Voltage: 20 … 35 V DC
• Power Consumption: ≤ 0.8 W
Field Side (Hazardous Area)
• Output Voltage: ≥ 16 V (@ 20 mA)
• Output Current: 4 … 20 mA (Overload 25 mA)
• Open Circuit Voltage: ≤ 28 V
Signal Characteristics
• Load Capacity: 0 … 550 Ω
• Response Time: ≤ 1 ms
• Insulation Voltage: 2.5 kV AC, 1 min
Environmental Conditions
• Operating Temperature: -20 … +60 °C (-4 … +140 °F)
• Storage Temperature: -40 … +80 °C
• Relative Humidity: 5 … 95 % RH (non-condensing)
• Protection Degree: IP20 (terminal side) in accordance with IEC
60529
• EMC: in accordance with EN 61326-1 (Industrial Locations)
Certifications and Compliance
• ATEX / IECEx: Ex ia IIC T4 Ga, Ex ia IIIC T135°C Da, Ex ia I Ma
• UL / FM / CSA: Class I, Division 1, Groups A-D; Class II,
Division 1, Groups E-G; Class III
• NEPSI / CCCF: China Explosion-Proof Conformity
Mechanical Data
• Dimensions: 12.5 × 106 × 128 mm (W × H × D)
• Weight: Approximately 100 g
• Mounting: 35 mm DIN rail (EN 60715)
• Terminals: Plug-in, 0.2 … 2.5 mm² solid or stranded wire
Typical Applications
• Petrochemical: Power supply and signal isolation for temperature,
pressure, differential pressure, and level transmitters in
refining, olefins, and aromatics plants. • Offshore platforms:
Sulfur gas detection and wellhead pressure monitoring on FPSOs and
drilling platforms.
• Fine chemicals: Explosion-proof circuits for reactor pH and flow
rate smart transmitters.
• Pharmaceuticals & Food: Hygienic pressure transmitters for clean
areas, isolating them from BMS/EMS systems.
• Utilities: Safety instrumented systems (SIS) for gas pressure
regulating stations, LNG storage tanks, and hydrogen refueling
stations.
Product details pictures
Related products
HiC2025A | HiC2025ES |
HiC2025HC | HiC2027 |
HiC2027DE | HiC2027ES |
HiC2441 | HiD2024 |
HiD2026 | HiD2022 |
HiD2022SK | HiD2030 |
HiD2030SK | KFD2-STC4-EX1 |
KFD2-STC4-EX2 | KFD2-STC5-EX2 |
KFD2-STC5-EX1 | KFD2-STV4-EX1-2 |
KCD2-STC-EX1-Y1 | KCD2-STC-EX1.ES.SP |
![]() |